ConduitCount

How many #10 THHN fit in 3-1/2" Flex?

18210 AWG THHN/THWN-2 wires in 3-1/2" Flexible metal conduit (FMC, Greenfield)

9.621 sq in × 40 % = 3.8484 sq in allowed. ÷ 0.0211 sq in per wire = 182.39, so 182.

182 #10 THHN in 3-1/2" Flex, drawn to scale

This pull in numbers

182 wires fill
39.9 % of 3-1/2" Flex
Limit for three or more
40 %
For 183 or more
4" Flex, up to 238
Pipe to wire diameter
21.34 to 1
In THW insulation
158 fit
In XHHW-2 insulation
158 fit

Before you pull 182

#10 THHN in other 3-1/2" conduit

ConduitInside areaMost #10 THHN
Electrical metallic tubing11.545219
Intermediate metal conduit10.584200
Rigid metal conduit (RMC, GRC)10.010189
Rigid PVC conduit, Schedule 409.737184
Rigid PVC conduit, Schedule 808.688164
Flexible metal conduit (FMC, Greenfield)9.621182
Liquidtight flexible metal conduit (LFMC)9.731184

#10 THHN in other Flex sizes

Other wire sizes in 3-1/2" Flex

Charts