ConduitCount

How many #12 THHN fit in 1-1/4" ENT?

4312 AWG THHN/THWN-2 wires in 1-1/4" Electrical nonmetallic tubing (smurf tube)

1.453 sq in × 40 % = 0.5812 sq in allowed. ÷ 0.0133 sq in per wire = 43.70, so 43.

43 #12 THHN in 1-1/4" ENT, drawn to scale

This pull in numbers

43 wires fill
39.4 % of 1-1/4" ENT
Limit for three or more
40 %
For 44 or more
1-1/2" ENT, up to 59
Pipe to wire diameter
10.46 to 1
In THW insulation
32 fit
In XHHW-2 insulation
32 fit

Before you pull 43

#12 THHN in other 1-1/4" conduit

#12 THHN in other ENT sizes

Other wire sizes in 1-1/4" ENT

Charts