ConduitCount

How many #6 THHN fit in 1-1/4" ENT?

116 AWG THHN/THWN-2 wires in 1-1/4" Electrical nonmetallic tubing (smurf tube)

1.453 sq in × 40 % = 0.5812 sq in allowed. ÷ 0.0507 sq in per wire = 11.46, so 11.

11 #6 THHN in 1-1/4" ENT, drawn to scale

This pull in numbers

11 wires fill
38.4 % of 1-1/4" ENT
Limit for three or more
40 %
For 12 or more
1-1/2" ENT, up to 15
Pipe to wire diameter
5.35 to 1
In THW insulation
8 fit
In XHHW-2 insulation
10 fit

Before you pull 11

#6 THHN in other 1-1/4" conduit

#6 THHN in other ENT sizes

Other wire sizes in 1-1/4" ENT

Charts