How many #1 THHN fit in 1-1/4" ENT?

31 AWG THHN/THWN-2 wires in 1-1/4" Electrical nonmetallic tubing (smurf tube)

1.453 sq in × 40 % = 0.5812 sq in allowed. ÷ 0.1562 sq in per wire = 3.72, so 3.

3 #1 THHN in 1-1/4" ENT, drawn to scale

This pull in numbers

3 wires fill
32.3 % of 1-1/4" ENT
Limit for three or more
40 %
For 4 or more
1-1/2" ENT, up to 5
Pipe to wire diameter
3.05 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 3.05 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.