ConduitCount

How many #10 THHN fit in 1-1/4" ENT?

2710 AWG THHN/THWN-2 wires in 1-1/4" Electrical nonmetallic tubing (smurf tube)

1.453 sq in × 40 % = 0.5812 sq in allowed. ÷ 0.0211 sq in per wire = 27.55, so 27.

27 #10 THHN in 1-1/4" ENT, drawn to scale

This pull in numbers

27 wires fill
39.2 % of 1-1/4" ENT
Limit for three or more
40 %
For 28 or more
1-1/2" ENT, up to 37
Pipe to wire diameter
8.29 to 1
In THW insulation
24 fit
In XHHW-2 insulation
24 fit

Before you pull 27

#10 THHN in other 1-1/4" conduit

#10 THHN in other ENT sizes

Other wire sizes in 1-1/4" ENT

Charts