ConduitCount

How many #12 THHN fit in 2-1/2" Flex?

14712 AWG THHN/THWN-2 wires in 2-1/2" Flexible metal conduit (FMC, Greenfield)

4.909 sq in × 40 % = 1.9636 sq in allowed. ÷ 0.0133 sq in per wire = 147.64, so 147.

147 #12 THHN in 2-1/2" Flex, drawn to scale

This pull in numbers

147 wires fill
39.8 % of 2-1/2" Flex
Limit for three or more
40 %
For 148 or more
3" Flex, up to 212
Pipe to wire diameter
19.23 to 1
In THW insulation
108 fit
In XHHW-2 insulation
108 fit

Before you pull 147

#12 THHN in other 2-1/2" conduit

ConduitInside areaMost #12 THHN
Electrical metallic tubing5.858176
Intermediate metal conduit5.135154
Rigid metal conduit (RMC, GRC)4.866146
Rigid PVC conduit, Schedule 404.695141
Rigid PVC conduit, Schedule 804.119124
Flexible metal conduit (FMC, Greenfield)4.909147
Liquidtight flexible metal conduit (LFMC)4.881146

#12 THHN in other Flex sizes

Other wire sizes in 2-1/2" Flex

Charts