ConduitCount

How many #4/0 THHN fit in 2-1/2" Flex?

64/0 AWG THHN/THWN-2 wires in 2-1/2" Flexible metal conduit (FMC, Greenfield)

4.909 sq in × 40 % = 1.9636 sq in allowed. ÷ 0.3237 sq in per wire = 6.07, so 6.

6 #4/0 THHN in 2-1/2" Flex, drawn to scale

This pull in numbers

6 wires fill
39.6 % of 2-1/2" Flex
Limit for three or more
40 %
For 7 or more
3" Flex, up to 8
Pipe to wire diameter
3.89 to 1
In THW insulation
5 fit
In XHHW-2 insulation
6 fit

Before you pull 6

#4/0 THHN in other 2-1/2" conduit

#4/0 THHN in other Flex sizes

Other wire sizes in 2-1/2" Flex

Charts