ConduitCount

How many #12 THHN fit in 2-1/2" PVC Sch 40?

14112 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 40

4.695 sq in × 40 % = 1.8780 sq in allowed. ÷ 0.0133 sq in per wire = 141.20, so 141.

141 #12 THHN in 2-1/2" PVC Sch 40, drawn to scale

This pull in numbers

141 wires fill
39.9 % of 2-1/2" PVC Sch 40
Limit for three or more
40 %
For 142 or more
3" PVC Sch 40, up to 218
Pipe to wire diameter
18.81 to 1
In THW insulation
103 fit
In XHHW-2 insulation
103 fit

Before you pull 141

#12 THHN in other 2-1/2" conduit

#12 THHN in other PVC Sch 40 sizes

Other wire sizes in 2-1/2" PVC Sch 40

Charts