244 AWG THHN/THWN-2 wires in 2-1/2" Flexible metal conduit (FMC, Greenfield)

4.909 sq in × 40 % = 1.9636 sq in allowed. ÷ 0.0824 sq in per wire = 23.83, which Note 7 rounds up to 24 because the decimal is 0.8 or more.

24 #4 THHN in 2-1/2" Flex, drawn to scale

This pull in numbers

24 wires fill
40.3 % of 2-1/2" Flex
Limit for three or more
40 %
For 25 or more
3" Flex, up to 34
Pipe to wire diameter
7.72 to 1