ConduitCount

How many #12 THHN fit in 2" IMC?

10912 AWG THHN/THWN-2 wires in 2" Intermediate metal conduit

3.630 sq in × 40 % = 1.4520 sq in allowed. ÷ 0.0133 sq in per wire = 109.17, so 109.

109 #12 THHN in 2" IMC, drawn to scale

This pull in numbers

109 wires fill
39.9 % of 2" IMC
Limit for three or more
40 %
For 110 or more
2-1/2" IMC, up to 154
Pipe to wire diameter
16.54 to 1
In THW insulation
80 fit
In XHHW-2 insulation
80 fit

Before you pull 109

#12 THHN in other 2" conduit

#12 THHN in other IMC sizes

Other wire sizes in 2" IMC

Charts