ConduitCount

How many #12 THHN fit in 3" PVC Sch 80?

19312 AWG THHN/THWN-2 wires in 3" Rigid PVC conduit, Schedule 80

6.442 sq in × 40 % = 2.5768 sq in allowed. ÷ 0.0133 sq in per wire = 193.74, so 193.

193 #12 THHN in 3" PVC Sch 80, drawn to scale

This pull in numbers

193 wires fill
39.8 % of 3" PVC Sch 80
Limit for three or more
40 %
For 194 or more
3-1/2" PVC Sch 80, up to 261
Pipe to wire diameter
22.03 to 1
In THW insulation
142 fit
In XHHW-2 insulation
142 fit

Before you pull 193

#12 THHN in other 3" conduit

ConduitInside areaMost #12 THHN
Electrical metallic tubing8.846266
Intermediate metal conduit7.922238
Rigid metal conduit (RMC, GRC)7.499225
Rigid PVC conduit, Schedule 407.268218
Rigid PVC conduit, Schedule 806.442193
Flexible metal conduit (FMC, Greenfield)7.069212
Liquidtight flexible metal conduit (LFMC)7.475225

#12 THHN in other PVC Sch 80 sizes

Other wire sizes in 3" PVC Sch 80

Charts