ConduitCount

How many 350 kcmil THHN fit in 3" PVC Sch 80?

5350 kcmil THHN/THWN-2 wires in 3" Rigid PVC conduit, Schedule 80

6.442 sq in × 40 % = 2.5768 sq in allowed. ÷ 0.5242 sq in per wire = 4.92, which Note 7 rounds up to 5 because the decimal is 0.8 or more.

5 350 kcmil THHN in 3" PVC Sch 80, drawn to scale

This pull in numbers

5 wires fill
40.7 % of 3" PVC Sch 80
Limit for three or more
40 %
For 6 or more
3-1/2" PVC Sch 80, up to 6
Pipe to wire diameter
3.51 to 1
In THW insulation
4 fit
In XHHW-2 insulation
5 fit

Before you pull 5

350 kcmil THHN in other 3" conduit

350 kcmil THHN in other PVC Sch 80 sizes

Other wire sizes in 3" PVC Sch 80

Charts