How many #2 THHN fit in 3" PVC Sch 80?
222 AWG THHN/THWN-2 wires in 3" Rigid PVC conduit, Schedule 80
6.442 sq in × 40 % = 2.5768 sq in allowed. ÷ 0.1158 sq in per wire = 22.25, so 22.
This pull in numbers
- 22 wires fill
- 39.5 % of 3" PVC Sch 80
- Limit for three or more
- 40 %
- For 23 or more
- 3-1/2" PVC Sch 80, up to 30
- Pipe to wire diameter
- 7.46 to 1
- In THW insulation
- 19 fit
- In XHHW-2 insulation
- 22 fit
Before you pull 22
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 22 is the total, not the hots.
- Derating. If all 22 were current-carrying, each would be adjusted to 45 % of its ampacity (Table 310.15(C)(1)): a #2 THHN at 130 A in the 90 °C column becomes 58.5 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#2 THHN in other 3" conduit
| Conduit | Inside area | Most #2 THHN |
|---|---|---|
| Electrical metallic tubing | 8.846 | 30 |
| Intermediate metal conduit | 7.922 | 27 |
| Rigid metal conduit (RMC, GRC) | 7.499 | 26 |
| Rigid PVC conduit, Schedule 40 | 7.268 | 25 |
| Rigid PVC conduit, Schedule 80 | 6.442 | 22 |
| Flexible metal conduit (FMC, Greenfield) | 7.069 | 24 |
| Liquidtight flexible metal conduit (LFMC) | 7.475 | 26 |
#2 THHN in other PVC Sch 80 sizes
Other wire sizes in 3" PVC Sch 80
#12: 193#10: 122#8: 70#6: 51#4: 31#3: 26#2: 22#1: 16#1/0: 14#2/0: 11#3/0: 9#4/0: 8250 kcmil: 6300 kcmil: 5350 kcmil: 5500 kcmil: 3