ConduitCount

How many #1/0 THHN fit in 3" PVC Sch 80?

141/0 AWG THHN/THWN-2 wires in 3" Rigid PVC conduit, Schedule 80

6.442 sq in × 40 % = 2.5768 sq in allowed. ÷ 0.1855 sq in per wire = 13.89, which Note 7 rounds up to 14 because the decimal is 0.8 or more.

14 #1/0 THHN in 3" PVC Sch 80, drawn to scale

This pull in numbers

14 wires fill
40.3 % of 3" PVC Sch 80
Limit for three or more
40 %
For 15 or more
3-1/2" PVC Sch 80, up to 18
Pipe to wire diameter
5.89 to 1
In THW insulation
11 fit
In XHHW-2 insulation
14 fit

Before you pull 14

#1/0 THHN in other 3" conduit

#1/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 3" PVC Sch 80

Charts