How many #1/0 THHN fit in 3" PVC Sch 80?
141/0 AWG THHN/THWN-2 wires in 3" Rigid PVC conduit, Schedule 80
6.442 sq in × 40 % = 2.5768 sq in allowed. ÷ 0.1855 sq in per wire = 13.89, which Note 7 rounds up to 14 because the decimal is 0.8 or more.
This pull in numbers
- 14 wires fill
- 40.3 % of 3" PVC Sch 80
- Limit for three or more
- 40 %
- For 15 or more
- 3-1/2" PVC Sch 80, up to 18
- Pipe to wire diameter
- 5.89 to 1
- In THW insulation
- 11 fit
- In XHHW-2 insulation
- 14 fit
Before you pull 14
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 14 is the total, not the hots.
- Derating. If all 14 were current-carrying, each would be adjusted to 50 % of its ampacity (Table 310.15(C)(1)): a #1/0 THHN at 170 A in the 90 °C column becomes 85 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#1/0 THHN in other 3" conduit
| Conduit | Inside area | Most #1/0 THHN |
|---|---|---|
| Electrical metallic tubing | 8.846 | 19 |
| Intermediate metal conduit | 7.922 | 17 |
| Rigid metal conduit (RMC, GRC) | 7.499 | 16 |
| Rigid PVC conduit, Schedule 40 | 7.268 | 15 |
| Rigid PVC conduit, Schedule 80 | 6.442 | 14 |
| Flexible metal conduit (FMC, Greenfield) | 7.069 | 15 |
| Liquidtight flexible metal conduit (LFMC) | 7.475 | 16 |
#1/0 THHN in other PVC Sch 80 sizes
Other wire sizes in 3" PVC Sch 80
#12: 193#10: 122#8: 70#6: 51#4: 31#3: 26#2: 22#1: 16#1/0: 14#2/0: 11#3/0: 9#4/0: 8250 kcmil: 6300 kcmil: 5350 kcmil: 5500 kcmil: 3