ConduitCount

How many #4/0 THHN fit in 3" PVC Sch 80?

84/0 AWG THHN/THWN-2 wires in 3" Rigid PVC conduit, Schedule 80

6.442 sq in × 40 % = 2.5768 sq in allowed. ÷ 0.3237 sq in per wire = 7.96, which Note 7 rounds up to 8 because the decimal is 0.8 or more.

8 #4/0 THHN in 3" PVC Sch 80, drawn to scale

This pull in numbers

8 wires fill
40.2 % of 3" PVC Sch 80
Limit for three or more
40 %
For 9 or more
3-1/2" PVC Sch 80, up to 10
Pipe to wire diameter
4.46 to 1
In THW insulation
7 fit
In XHHW-2 insulation
8 fit

Before you pull 8

#4/0 THHN in other 3" conduit

#4/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 3" PVC Sch 80

Charts