ConduitCount

How many 250 kcmil THHN fit in 3" PVC Sch 80?

6250 kcmil THHN/THWN-2 wires in 3" Rigid PVC conduit, Schedule 80

6.442 sq in × 40 % = 2.5768 sq in allowed. ÷ 0.3970 sq in per wire = 6.49, so 6.

6 250 kcmil THHN in 3" PVC Sch 80, drawn to scale

This pull in numbers

6 wires fill
37.0 % of 3" PVC Sch 80
Limit for three or more
40 %
For 7 or more
3-1/2" PVC Sch 80, up to 8
Pipe to wire diameter
4.03 to 1
In THW insulation
5 fit
In XHHW-2 insulation
6 fit

Before you pull 6

250 kcmil THHN in other 3" conduit

250 kcmil THHN in other PVC Sch 80 sizes

Other wire sizes in 3" PVC Sch 80

Charts