How many #14 THHN fit in 1/2" IMC?

1414 AWG THHN/THWN-2 wires in 1/2" Intermediate metal conduit

0.342 sq in × 40 % = 0.1368 sq in allowed. ÷ 0.0097 sq in per wire = 14.10, so 14.

14 #14 THHN in 1/2" IMC, drawn to scale

This pull in numbers

14 wires fill
39.7 % of 1/2" IMC
Limit for three or more
40 %
For 15 or more
3/4" IMC, up to 24
Pipe to wire diameter
5.95 to 1
In THW insulation
10 fit
In XHHW-2 insulation
10 fit

Before you pull 14

#14 THHN in other 1/2" conduit

#14 THHN in other IMC sizes

Other wire sizes in 1/2" IMC