ConduitCount

How many #2/0 THHN fit in 4" Rigid?

232/0 AWG THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)

12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.2223 sq in per wire = 23.18, so 23.

23 #2/0 THHN in 4" Rigid, drawn to scale

This pull in numbers

23 wires fill
39.7 % of 4" Rigid
Limit for three or more
40 %
For 24 or more
5" Rigid, up to 36
Pipe to wire diameter
7.61 to 1
In THW insulation
19 fit
In XHHW-2 insulation
23 fit

Before you pull 23

#2/0 THHN in other 4" conduit

#2/0 THHN in other Rigid sizes

Other wire sizes in 4" Rigid

Charts