ConduitCount

How many #3/0 THHN fit in 3-1/2" Liquidtight?

143/0 AWG THHN/THWN-2 wires in 3-1/2" Liquidtight flexible metal conduit (LFMC)

9.731 sq in × 40 % = 3.8924 sq in allowed. ÷ 0.2679 sq in per wire = 14.53, so 14.

14 #3/0 THHN in 3-1/2" Liquidtight, drawn to scale

This pull in numbers

14 wires fill
38.5 % of 3-1/2" Liquidtight
Limit for three or more
40 %
For 15 or more
4" Liquidtight, up to 19
Pipe to wire diameter
6.03 to 1
In THW insulation
12 fit
In XHHW-2 insulation
14 fit

Before you pull 14

#3/0 THHN in other 3-1/2" conduit

ConduitInside areaMost #3/0 THHN
Electrical metallic tubing11.54517
Intermediate metal conduit10.58416
Rigid metal conduit (RMC, GRC)10.01015
Rigid PVC conduit, Schedule 409.73714
Rigid PVC conduit, Schedule 808.68813
Flexible metal conduit (FMC, Greenfield)9.62114
Liquidtight flexible metal conduit (LFMC)9.73114

#3/0 THHN in other Liquidtight sizes

Other wire sizes in 3-1/2" Liquidtight

Charts