How many #3/0 THHN fit in 3-1/2" PVC Sch 40?

143/0 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 40

9.737 sq in × 40 % = 3.8948 sq in allowed. ÷ 0.2679 sq in per wire = 14.54, so 14.

14 #3/0 THHN in 3-1/2" PVC Sch 40, drawn to scale

This pull in numbers

14 wires fill
38.5 % of 3-1/2" PVC Sch 40
Limit for three or more
40 %
For 15 or more
4" PVC Sch 40, up to 18
Pipe to wire diameter
6.03 to 1
In THW insulation
12 fit
In XHHW-2 insulation
14 fit

Before you pull 14

#3/0 THHN in other 3-1/2" conduit

#3/0 THHN in other PVC Sch 40 sizes

Other wire sizes in 3-1/2" PVC Sch 40