How many #3/0 THHN fit in 3-1/2" Rigid?
153/0 AWG THHN/THWN-2 wires in 3-1/2" Rigid metal conduit (RMC, GRC)
10.010 sq in × 40 % = 4.0040 sq in allowed. ÷ 0.2679 sq in per wire = 14.95, which Note 7 rounds up to 15 because the decimal is 0.8 or more.
This pull in numbers
- 15 wires fill
- 40.1 % of 3-1/2" Rigid
- Limit for three or more
- 40 %
- For 16 or more
- 4" Rigid, up to 19
- Pipe to wire diameter
- 6.11 to 1
- In THW insulation
- 13 fit
- In XHHW-2 insulation
- 15 fit
Before you pull 15
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 15 is the total, not the hots.
- Derating. If all 15 were current-carrying, each would be adjusted to 50 % of its ampacity (Table 310.15(C)(1)): a #3/0 THHN at 225 A in the 90 °C column becomes 112.5 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#3/0 THHN in other 3-1/2" conduit
| Conduit | Inside area | Most #3/0 THHN |
|---|---|---|
| Electrical metallic tubing | 11.545 | 17 |
| Intermediate metal conduit | 10.584 | 16 |
| Rigid metal conduit (RMC, GRC) | 10.010 | 15 |
| Rigid PVC conduit, Schedule 40 | 9.737 | 14 |
| Rigid PVC conduit, Schedule 80 | 8.688 | 13 |
| Flexible metal conduit (FMC, Greenfield) | 9.621 | 14 |
| Liquidtight flexible metal conduit (LFMC) | 9.731 | 14 |
#3/0 THHN in other Rigid sizes
Other wire sizes in 3-1/2" Rigid
#10: 189#8: 109#6: 79#4: 48#3: 41#2: 34#1: 25#1/0: 21#2/0: 18#3/0: 15#4/0: 12250 kcmil: 10300 kcmil: 8350 kcmil: 7500 kcmil: 5