How many #1 THHN fit in 3-1/2" Liquidtight?
251 AWG THHN/THWN-2 wires in 3-1/2" Liquidtight flexible metal conduit (LFMC)
9.731 sq in × 40 % = 3.8924 sq in allowed. ÷ 0.1562 sq in per wire = 24.92, which Note 7 rounds up to 25 because the decimal is 0.8 or more.
This pull in numbers
- 25 wires fill
- 40.1 % of 3-1/2" Liquidtight
- Limit for three or more
- 40 %
- For 26 or more
- 4" Liquidtight, up to 32
- Pipe to wire diameter
- 7.89 to 1
- In THW insulation
- 20 fit
- In XHHW-2 insulation
- 25 fit
Before you pull 25
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 25 is the total, not the hots.
- Derating. If all 25 were current-carrying, each would be adjusted to 45 % of its ampacity (Table 310.15(C)(1)): a #1 THHN at 145 A in the 90 °C column becomes 65.3 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#1 THHN in other 3-1/2" conduit
| Conduit | Inside area | Most #1 THHN |
|---|---|---|
| Electrical metallic tubing | 11.545 | 29 |
| Intermediate metal conduit | 10.584 | 27 |
| Rigid metal conduit (RMC, GRC) | 10.010 | 25 |
| Rigid PVC conduit, Schedule 40 | 9.737 | 25 |
| Rigid PVC conduit, Schedule 80 | 8.688 | 22 |
| Flexible metal conduit (FMC, Greenfield) | 9.621 | 24 |
| Liquidtight flexible metal conduit (LFMC) | 9.731 | 25 |
#1 THHN in other Liquidtight sizes
Other wire sizes in 3-1/2" Liquidtight
#10: 184#8: 106#6: 76#4: 47#3: 40#2: 33#1: 25#1/0: 21#2/0: 17#3/0: 14#4/0: 12250 kcmil: 10300 kcmil: 8350 kcmil: 7500 kcmil: 5