ConduitCount

How many #3/0 THHN fit in 3-1/2" PVC Sch 80?

133/0 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 80

8.688 sq in × 40 % = 3.4752 sq in allowed. ÷ 0.2679 sq in per wire = 12.97, which Note 7 rounds up to 13 because the decimal is 0.8 or more.

13 #3/0 THHN in 3-1/2" PVC Sch 80, drawn to scale

This pull in numbers

13 wires fill
40.1 % of 3-1/2" PVC Sch 80
Limit for three or more
40 %
For 14 or more
4" PVC Sch 80, up to 17
Pipe to wire diameter
5.70 to 1
In THW insulation
11 fit
In XHHW-2 insulation
13 fit

Before you pull 13

#3/0 THHN in other 3-1/2" conduit

#3/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 3-1/2" PVC Sch 80

Charts