ConduitCount

How many #2 THHN fit in 3-1/2" Liquidtight?

332 AWG THHN/THWN-2 wires in 3-1/2" Liquidtight flexible metal conduit (LFMC)

9.731 sq in × 40 % = 3.8924 sq in allowed. ÷ 0.1158 sq in per wire = 33.61, so 33.

33 #2 THHN in 3-1/2" Liquidtight, drawn to scale

This pull in numbers

33 wires fill
39.3 % of 3-1/2" Liquidtight
Limit for three or more
40 %
For 34 or more
4" Liquidtight, up to 44
Pipe to wire diameter
9.17 to 1
In THW insulation
29 fit
In XHHW-2 insulation
34 fit

Before you pull 33

#2 THHN in other 3-1/2" conduit

ConduitInside areaMost #2 THHN
Electrical metallic tubing11.54540
Intermediate metal conduit10.58436
Rigid metal conduit (RMC, GRC)10.01034
Rigid PVC conduit, Schedule 409.73733
Rigid PVC conduit, Schedule 808.68830
Flexible metal conduit (FMC, Greenfield)9.62133
Liquidtight flexible metal conduit (LFMC)9.73133

#2 THHN in other Liquidtight sizes

Other wire sizes in 3-1/2" Liquidtight

Charts