ConduitCount

How many #3/0 THHN fit in 3/4" IMC?

13/0 AWG THHN/THWN-2 wires in 3/4" Intermediate metal conduit

0.586 sq in × 53 % = 0.3106 sq in allowed. ÷ 0.2679 sq in per wire = 1.16.

1 #3/0 THHN in 3/4" IMC, drawn to scale

This pull in numbers

1 wires fill
45.7 % of 3/4" IMC
Limit for one
53 %
For 2 or more
1-1/2" IMC, up to 3
Pipe to wire diameter
1.48 to 1
In THW insulation
0 fit
In XHHW-2 insulation
1 fit

Before you pull 1

#3/0 THHN in other 3/4" conduit

#3/0 THHN in other IMC sizes

Other wire sizes in 3/4" IMC