Intermediate metal conduit fill chart

The most THHN wires of one size each IMC size may hold, with three or more wires at 40 % fill. Pick a size for XHHW-2 and THW as well.

Trade sizeInside area40 %#14#12#10#8#6#4#2#1/0#4/0250 kcmil500 kcmil
1/2"0.3420.1371410632110000
3/4"0.5860.23424171164311000
1"0.9590.384392918107431110
1-1/4"1.6470.6596849311813853111
1-1/2"2.2250.89091674224171174211
2"3.6301.45214910969392817128431
2-1/2"5.1352.054211154975640251711653
3"7.9223.1693262381508662382717984
3-1/2"10.5844.2344363182001158351362313106
4"13.6315.45256241025814910766472917137

Areas in square inches, from Chapter 9, Table 4 (2023 NEC). THHN/THWN-2 areas from Table 5.

About IMC

IMC has a thinner wall than rigid, so it has a little more room inside size for size. Support follows 342.30: within 3 ft of each box, then every 10 ft, or longer on straight runs with threaded couplings. See strap spacing and the fill rules.