ConduitCount

How many #3/0 THHN fit in 3/4" Rigid?

13/0 AWG THHN/THWN-2 wires in 3/4" Rigid metal conduit (RMC, GRC)

0.549 sq in × 53 % = 0.2910 sq in allowed. ÷ 0.2679 sq in per wire = 1.09.

1 #3/0 THHN in 3/4" Rigid, drawn to scale

This pull in numbers

1 wires fill
48.8 % of 3/4" Rigid
Limit for one
53 %
For 2 or more
1-1/2" Rigid, up to 3
Pipe to wire diameter
1.43 to 1
In THW insulation
0 fit
In XHHW-2 insulation
1 fit

Before you pull 1

#3/0 THHN in other 3/4" conduit

ConduitInside areaMost #3/0 THHN
Electrical metallic tubing0.5331
Intermediate metal conduit0.5861
Rigid metal conduit (RMC, GRC)0.5491
Rigid PVC conduit, Schedule 400.5081
Rigid PVC conduit, Schedule 800.4090
Flexible metal conduit (FMC, Greenfield)0.5331
Liquidtight flexible metal conduit (LFMC)0.5411
Electrical nonmetallic tubing (smurf tube)0.5081

#3/0 THHN in other Rigid sizes

Other wire sizes in 3/4" Rigid

Charts