ConduitCount

How many #3/0 THHN fit in 4" IMC?

203/0 AWG THHN/THWN-2 wires in 4" Intermediate metal conduit

13.631 sq in × 40 % = 5.4524 sq in allowed. ÷ 0.2679 sq in per wire = 20.35, so 20.

20 #3/0 THHN in 4" IMC, drawn to scale

This pull in numbers

20 wires fill
39.3 % of 4" IMC
Limit for three or more
40 %
For 21 or more
no bigger IMC
Pipe to wire diameter
7.13 to 1
In THW insulation
17 fit
In XHHW-2 insulation
20 fit

Before you pull 20

#3/0 THHN in other 4" conduit

#3/0 THHN in other IMC sizes

Other wire sizes in 4" IMC

Charts