ConduitCount

How many #3 THHN fit in 3/4" IMC?

13 AWG THHN/THWN-2 wires in 3/4" Intermediate metal conduit

0.586 sq in × 53 % = 0.3106 sq in allowed. ÷ 0.0973 sq in per wire = 3.19.

1 #3 THHN in 3/4" IMC, drawn to scale

This pull in numbers

1 wires fill
16.6 % of 3/4" IMC
Limit for one
53 %
For 2 or more
1" IMC, up to 4
Pipe to wire diameter
2.45 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

#3 THHN in other 3/4" conduit

#3 THHN in other IMC sizes

Other wire sizes in 3/4" IMC

Charts