73/0 AWG THHN/THWN-2 wires in 2-1/2" Intermediate metal conduit

5.135 sq in × 40 % = 2.0540 sq in allowed. ÷ 0.2679 sq in per wire = 7.67, so 7.

7 #3/0 THHN in 2-1/2" IMC, drawn to scale

This pull in numbers

7 wires fill
36.5 % of 2-1/2" IMC
Limit for three or more
40 %
For 8 or more
3" IMC, up to 12
Pipe to wire diameter
4.38 to 1
In THW insulation
6 fit
In XHHW-2 insulation
7 fit

Before you pull 7

#3/0 THHN in other 2-1/2" conduit

#3/0 THHN in other IMC sizes

Other wire sizes in 2-1/2" IMC