How many #8 THHN fit in 3/4" IMC?

68 AWG THHN/THWN-2 wires in 3/4" Intermediate metal conduit

0.586 sq in × 40 % = 0.2344 sq in allowed. ÷ 0.0366 sq in per wire = 6.40, so 6.

6 #8 THHN in 3/4" IMC, drawn to scale

This pull in numbers

6 wires fill
37.5 % of 3/4" IMC
Limit for three or more
40 %
For 7 or more
1" IMC, up to 10
Pipe to wire diameter
4.00 to 1
In THW insulation
5 fit
In XHHW-2 insulation
5 fit

Before you pull 6

#8 THHN in other 3/4" conduit

#8 THHN in other IMC sizes