ConduitCount

How many #6 THHN fit in 3/4" IMC?

46 AWG THHN/THWN-2 wires in 3/4" Intermediate metal conduit

0.586 sq in × 40 % = 0.2344 sq in allowed. ÷ 0.0507 sq in per wire = 4.62, so 4.

4 #6 THHN in 3/4" IMC, drawn to scale

This pull in numbers

4 wires fill
34.6 % of 3/4" IMC
Limit for three or more
40 %
For 5 or more
1" IMC, up to 7
Pipe to wire diameter
3.40 to 1
In THW insulation
3 fit
In XHHW-2 insulation
4 fit

Before you pull 4

#6 THHN in other 3/4" conduit

#6 THHN in other IMC sizes

Other wire sizes in 3/4" IMC

Charts