ConduitCount

How many #3/0 THHN fit in 4" Rigid?

193/0 AWG THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)

12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.2679 sq in per wire = 19.23, so 19.

19 #3/0 THHN in 4" Rigid, drawn to scale

This pull in numbers

19 wires fill
39.5 % of 4" Rigid
Limit for three or more
40 %
For 20 or more
5" Rigid, up to 30
Pipe to wire diameter
6.93 to 1
In THW insulation
16 fit
In XHHW-2 insulation
19 fit

Before you pull 19

#3/0 THHN in other 4" conduit

#3/0 THHN in other Rigid sizes

Other wire sizes in 4" Rigid