ConduitCount

How many #3/0 THHN fit in 1-1/2" Rigid?

33/0 AWG THHN/THWN-2 wires in 1-1/2" Rigid metal conduit (RMC, GRC)

2.071 sq in × 40 % = 0.8284 sq in allowed. ÷ 0.2679 sq in per wire = 3.09, so 3.

3 #3/0 THHN in 1-1/2" Rigid, drawn to scale

This pull in numbers

3 wires fill
38.8 % of 1-1/2" Rigid
Limit for three or more
40 %
For 4 or more
2" Rigid, up to 5
Pipe to wire diameter
2.78 to 1
In THW insulation
2 fit
In XHHW-2 insulation
3 fit

Before you pull 3

#3/0 THHN in other 1-1/2" conduit

#3/0 THHN in other Rigid sizes

Other wire sizes in 1-1/2" Rigid

Charts