ConduitCount

How many #3/0 THHN fit in 4" EMT?

223/0 AWG THHN/THWN-2 wires in 4" Electrical metallic tubing

14.753 sq in × 40 % = 5.9012 sq in allowed. ÷ 0.2679 sq in per wire = 22.03, so 22.

22 #3/0 THHN in 4" EMT, drawn to scale

This pull in numbers

22 wires fill
39.9 % of 4" EMT
Limit for three or more
40 %
For 23 or more
no bigger EMT
Pipe to wire diameter
7.42 to 1
In THW insulation
19 fit
In XHHW-2 insulation
22 fit

Before you pull 22

#3/0 THHN in other 4" conduit

#3/0 THHN in other EMT sizes

Other wire sizes in 4" EMT

Charts