ConduitCount

How many #4/0 THHN fit in 3-1/2" Flex?

124/0 AWG THHN/THWN-2 wires in 3-1/2" Flexible metal conduit (FMC, Greenfield)

9.621 sq in × 40 % = 3.8484 sq in allowed. ÷ 0.3237 sq in per wire = 11.89, which Note 7 rounds up to 12 because the decimal is 0.8 or more.

12 #4/0 THHN in 3-1/2" Flex, drawn to scale

This pull in numbers

12 wires fill
40.4 % of 3-1/2" Flex
Limit for three or more
40 %
For 13 or more
4" Flex, up to 15
Pipe to wire diameter
5.45 to 1
In THW insulation
10 fit
In XHHW-2 insulation
12 fit

Before you pull 12

#4/0 THHN in other 3-1/2" conduit

ConduitInside areaMost #4/0 THHN
Electrical metallic tubing11.54514
Intermediate metal conduit10.58413
Rigid metal conduit (RMC, GRC)10.01012
Rigid PVC conduit, Schedule 409.73712
Rigid PVC conduit, Schedule 808.68810
Flexible metal conduit (FMC, Greenfield)9.62112
Liquidtight flexible metal conduit (LFMC)9.73112

#4/0 THHN in other Flex sizes

Other wire sizes in 3-1/2" Flex

Charts