64/0 AWG THHN/THWN-2 wires in 2-1/2" Intermediate metal conduit

5.135 sq in × 40 % = 2.0540 sq in allowed. ÷ 0.3237 sq in per wire = 6.35, so 6.

6 #4/0 THHN in 2-1/2" IMC, drawn to scale

This pull in numbers

6 wires fill
37.8 % of 2-1/2" IMC
Limit for three or more
40 %
For 7 or more
3" IMC, up to 9
Pipe to wire diameter
3.98 to 1
In THW insulation
5 fit
In XHHW-2 insulation
6 fit