ConduitCount

How many #4 THHN fit in 6" PVC Sch 80?

1244 AWG THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 80

25.598 sq in × 40 % = 10.2392 sq in allowed. ÷ 0.0824 sq in per wire = 124.26, so 124.

124 #4 THHN in 6" PVC Sch 80, drawn to scale

This pull in numbers

124 wires fill
39.9 % of 6" PVC Sch 80
Limit for three or more
40 %
For 125 or more
no bigger PVC Sch 80
Pipe to wire diameter
17.62 to 1
In THW insulation
105 fit
In XHHW-2 insulation
125 fit

Before you pull 124

#4 THHN in other 6" conduit

ConduitInside areaMost #4 THHN
Rigid metal conduit (RMC, GRC)29.158141
Rigid PVC conduit, Schedule 4028.567138
Rigid PVC conduit, Schedule 8025.598124

#4 THHN in other PVC Sch 80 sizes

Other wire sizes in 6" PVC Sch 80

Charts