ConduitCount

How many #4 THHN fit in 2-1/2" PVC Sch 80?

204 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 80

4.119 sq in × 40 % = 1.6476 sq in allowed. ÷ 0.0824 sq in per wire = 20.00, which Note 7 rounds up to 20 because the decimal is 0.8 or more.

20 #4 THHN in 2-1/2" PVC Sch 80, drawn to scale

This pull in numbers

20 wires fill
40.0 % of 2-1/2" PVC Sch 80
Limit for three or more
40 %
For 21 or more
3" PVC Sch 80, up to 31
Pipe to wire diameter
7.07 to 1
In THW insulation
17 fit
In XHHW-2 insulation
20 fit

Before you pull 20

#4 THHN in other 2-1/2" conduit

#4 THHN in other PVC Sch 80 sizes

Other wire sizes in 2-1/2" PVC Sch 80

Charts