ConduitCount

How many #4 THHN fit in 4" PVC Sch 80?

544 AWG THHN/THWN-2 wires in 4" Rigid PVC conduit, Schedule 80

11.258 sq in × 40 % = 4.5032 sq in allowed. ÷ 0.0824 sq in per wire = 54.65, so 54.

54 #4 THHN in 4" PVC Sch 80, drawn to scale

This pull in numbers

54 wires fill
39.5 % of 4" PVC Sch 80
Limit for three or more
40 %
For 55 or more
5" PVC Sch 80, up to 86
Pipe to wire diameter
11.69 to 1
In THW insulation
46 fit
In XHHW-2 insulation
55 fit

Before you pull 54

#4 THHN in other 4" conduit

#4 THHN in other PVC Sch 80 sizes

Other wire sizes in 4" PVC Sch 80

Charts