ConduitCount

How many #4 THHN fit in 2" PVC Sch 80?

144 AWG THHN/THWN-2 wires in 2" Rigid PVC conduit, Schedule 80

2.874 sq in × 40 % = 1.1496 sq in allowed. ÷ 0.0824 sq in per wire = 13.95, which Note 7 rounds up to 14 because the decimal is 0.8 or more.

14 #4 THHN in 2" PVC Sch 80, drawn to scale

This pull in numbers

14 wires fill
40.1 % of 2" PVC Sch 80
Limit for three or more
40 %
For 15 or more
2-1/2" PVC Sch 80, up to 20
Pipe to wire diameter
5.90 to 1
In THW insulation
12 fit
In XHHW-2 insulation
14 fit

Before you pull 14

#4 THHN in other 2" conduit

#4 THHN in other PVC Sch 80 sizes

Other wire sizes in 2" PVC Sch 80

Charts