ConduitCount

How many #4 THHN fit in 2-1/2" Liquidtight?

234 AWG THHN/THWN-2 wires in 2-1/2" Liquidtight flexible metal conduit (LFMC)

4.881 sq in × 40 % = 1.9524 sq in allowed. ÷ 0.0824 sq in per wire = 23.69, so 23.

23 #4 THHN in 2-1/2" Liquidtight, drawn to scale

This pull in numbers

23 wires fill
38.8 % of 2-1/2" Liquidtight
Limit for three or more
40 %
For 24 or more
3" Liquidtight, up to 36
Pipe to wire diameter
7.69 to 1
In THW insulation
20 fit
In XHHW-2 insulation
24 fit

Before you pull 23

#4 THHN in other 2-1/2" conduit

ConduitInside areaMost #4 THHN
Electrical metallic tubing5.85828
Intermediate metal conduit5.13525
Rigid metal conduit (RMC, GRC)4.86623
Rigid PVC conduit, Schedule 404.69522
Rigid PVC conduit, Schedule 804.11920
Flexible metal conduit (FMC, Greenfield)4.90924
Liquidtight flexible metal conduit (LFMC)4.88123

#4 THHN in other Liquidtight sizes

Other wire sizes in 2-1/2" Liquidtight

Charts