How many #4 THHN fit in 2-1/2" IMC?

254 AWG THHN/THWN-2 wires in 2-1/2" Intermediate metal conduit

5.135 sq in × 40 % = 2.0540 sq in allowed. ÷ 0.0824 sq in per wire = 24.93, which Note 7 rounds up to 25 because the decimal is 0.8 or more.

25 #4 THHN in 2-1/2" IMC, drawn to scale

This pull in numbers

25 wires fill
40.1 % of 2-1/2" IMC
Limit for three or more
40 %
For 26 or more
3" IMC, up to 38
Pipe to wire diameter
7.89 to 1
In THW insulation
21 fit
In XHHW-2 insulation
25 fit

Before you pull 25

#4 THHN in other 2-1/2" conduit

#4 THHN in other IMC sizes

Other wire sizes in 2-1/2" IMC

Charts