ConduitCount

How many #4 THHN fit in 6" Rigid?

1414 AWG THHN/THWN-2 wires in 6" Rigid metal conduit (RMC, GRC)

29.158 sq in × 40 % = 11.6632 sq in allowed. ÷ 0.0824 sq in per wire = 141.54, so 141.

141 #4 THHN in 6" Rigid, drawn to scale

This pull in numbers

141 wires fill
39.8 % of 6" Rigid
Limit for three or more
40 %
For 142 or more
no bigger Rigid
Pipe to wire diameter
18.81 to 1
In THW insulation
120 fit
In XHHW-2 insulation
143 fit

Before you pull 141

#4 THHN in other 6" conduit

ConduitInside areaMost #4 THHN
Rigid metal conduit (RMC, GRC)29.158141
Rigid PVC conduit, Schedule 4028.567138
Rigid PVC conduit, Schedule 8025.598124

#4 THHN in other Rigid sizes

Other wire sizes in 6" Rigid

Charts