ConduitCount

How many #4 THHN fit in 3-1/2" Rigid?

484 AWG THHN/THWN-2 wires in 3-1/2" Rigid metal conduit (RMC, GRC)

10.010 sq in × 40 % = 4.0040 sq in allowed. ÷ 0.0824 sq in per wire = 48.59, so 48.

48 #4 THHN in 3-1/2" Rigid, drawn to scale

This pull in numbers

48 wires fill
39.5 % of 3-1/2" Rigid
Limit for three or more
40 %
For 49 or more
4" Rigid, up to 62
Pipe to wire diameter
11.02 to 1
In THW insulation
41 fit
In XHHW-2 insulation
49 fit

Before you pull 48

#4 THHN in other 3-1/2" conduit

#4 THHN in other Rigid sizes

Other wire sizes in 3-1/2" Rigid

Charts