ConduitCount

How many #4 THHN fit in 3" Rigid?

364 AWG THHN/THWN-2 wires in 3" Rigid metal conduit (RMC, GRC)

7.499 sq in × 40 % = 2.9996 sq in allowed. ÷ 0.0824 sq in per wire = 36.40, so 36.

36 #4 THHN in 3" Rigid, drawn to scale

This pull in numbers

36 wires fill
39.6 % of 3" Rigid
Limit for three or more
40 %
For 37 or more
3-1/2" Rigid, up to 48
Pipe to wire diameter
9.54 to 1
In THW insulation
31 fit
In XHHW-2 insulation
37 fit

Before you pull 36

#4 THHN in other 3" conduit

#4 THHN in other Rigid sizes

Other wire sizes in 3" Rigid

Charts