ConduitCount

How many #1/0 THHN fit in 6" Rigid?

631/0 AWG THHN/THWN-2 wires in 6" Rigid metal conduit (RMC, GRC)

29.158 sq in × 40 % = 11.6632 sq in allowed. ÷ 0.1855 sq in per wire = 62.87, which Note 7 rounds up to 63 because the decimal is 0.8 or more.

63 #1/0 THHN in 6" Rigid, drawn to scale

This pull in numbers

63 wires fill
40.1 % of 6" Rigid
Limit for three or more
40 %
For 64 or more
no bigger Rigid
Pipe to wire diameter
12.54 to 1
In THW insulation
52 fit
In XHHW-2 insulation
64 fit

Before you pull 63

#1/0 THHN in other 6" conduit

ConduitInside areaMost #1/0 THHN
Rigid metal conduit (RMC, GRC)29.15863
Rigid PVC conduit, Schedule 4028.56761
Rigid PVC conduit, Schedule 8025.59855

#1/0 THHN in other Rigid sizes

Other wire sizes in 6" Rigid

Charts