1002 AWG THHN/THWN-2 wires in 6" Rigid metal conduit (RMC, GRC)

29.158 sq in × 40 % = 11.6632 sq in allowed. ÷ 0.1158 sq in per wire = 100.72, so 100.

100 #2 THHN in 6" Rigid, drawn to scale

This pull in numbers

100 wires fill
39.7 % of 6" Rigid
Limit for three or more
40 %
For 101 or more
no bigger Rigid
Pipe to wire diameter
15.87 to 1
In THW insulation
87 fit
In XHHW-2 insulation
101 fit

Before you pull 100

#2 THHN in other 6" conduit

ConduitInside areaMost #2 THHN
Rigid metal conduit (RMC, GRC)29.158100
Rigid PVC conduit, Schedule 4028.56798
Rigid PVC conduit, Schedule 8025.59888

#2 THHN in other Rigid sizes

Other wire sizes in 6" Rigid

Charts