ConduitCount

How many 500 kcmil THHN fit in 4" IMC?

7500 kcmil THHN/THWN-2 wires in 4" Intermediate metal conduit

13.631 sq in × 40 % = 5.4524 sq in allowed. ÷ 0.7073 sq in per wire = 7.71, so 7.

7 500 kcmil THHN in 4" IMC, drawn to scale

This pull in numbers

7 wires fill
36.3 % of 4" IMC
Limit for three or more
40 %
For 8 or more
no bigger IMC
Pipe to wire diameter
4.39 to 1
In THW insulation
7 fit
In XHHW-2 insulation
8 fit

Before you pull 7

500 kcmil THHN in other 4" conduit

500 kcmil THHN in other IMC sizes

Other wire sizes in 4" IMC

Charts