442 AWG THHN/THWN-2 wires in 4" Liquidtight flexible metal conduit (LFMC)

12.692 sq in × 40 % = 5.0768 sq in allowed. ÷ 0.1158 sq in per wire = 43.84, which Note 7 rounds up to 44 because the decimal is 0.8 or more.

44 #2 THHN in 4" Liquidtight, drawn to scale

This pull in numbers

44 wires fill
40.1 % of 4" Liquidtight
Limit for three or more
40 %
For 45 or more
no bigger Liquidtight
Pipe to wire diameter
10.47 to 1
In THW insulation
38 fit
In XHHW-2 insulation
44 fit

Before you pull 44

#2 THHN in other 4" conduit

ConduitInside areaMost #2 THHN
Electrical metallic tubing14.75351
Intermediate metal conduit13.63147
Rigid metal conduit (RMC, GRC)12.88244
Rigid PVC conduit, Schedule 4012.55443
Rigid PVC conduit, Schedule 8011.25839
Flexible metal conduit (FMC, Greenfield)12.56643
Liquidtight flexible metal conduit (LFMC)12.69244

#2 THHN in other Liquidtight sizes